  1. the pressure block installation height must be consistent, usually in the level above the 150 ~ 200mm;;
  2. the pressure block welding requirements with three-sided spot welding, thermocouple insertion port do not spot welding, side spot welding to pay attention to the stop screws will not be welded to death.
  3. Pipe wall temperature should be installed symmetrically up and down.
  4. armoured thermocouple must be inserted into place, stop screws tightened in place.
  5. armoured thermocouple lead recommended to use a small slot box.
  6. armoured thermocouple fixed stainless steel wire must be used instead of;
  7. armoured thermocouple and furnace wall interface must be wrapped, and then threaded into the homemade protection tube leads;
  8. in order to prevent the boiler from settling, it is recommended to use the transition junction box, and then connected to the pre-positioner with a compensating wire.
  9. furnace wall and pre-positioning of the bridge or protection pipe should not be closed, to prevent high heat flow directly into the pre-positioning and damage to the components inside (Tianjin Electric Construction did not pay attention to, resulting in damage to the pre-positioning);;.
  10. the preamplifier installation location can not be too far, otherwise the length of the thermocouple is not enough;;.
  11. wiring should be correct, reliable.